• ADM loop technology with
System Sensor/200 protocol
• One input with line-monitoring for
wire breakage and short circuit
• Status LED
• Setting of module address via
decadic rotary switches
• Mounting in module box or by means
of mounting base
Description
The addressable Monitor Module M210E serves for the
line-monitored integration of contact detectors, such as
manual call points, sprinkler system contacts or super-
vising contacts, into the bidirectional communication
on the ADM loop with System Sensor/200 protocol.
A status LED indicates the condition of the monitor
module. Separate terminals enable the operation of
the module with or without the integrated dual-isolator.
Accessories for mounting on a wall, on a plate or on a
DIN rail are available.
Specifications
Operating voltage
Current consumption
Ambient temperature
Dimensions L × W × H
Colour
Supply through loop voltage
approx. 510µA (quiescent)
-20°C to +60°C
93 × 94 × 23 (mm)
cream
Weight
110g
Approval
VdS G202140
Order number
Order name
249100
Monitor Module 1xSurv.In/Anal./200/SS M210E
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
M210E_DBL_LST_EN_0804.PDF • PAGE 1
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
|
Kyocera Photo Printer FS 2000D FS 3900DN FS 4000DN FS 6950DN User Manual
La Crosse Technology Portable Radio WD 3106UR B User Manual
La Crosse Technology Weather Radio WS 9020U 915MHZ User Manual
Lego Games 10572 User Manual
Lenoxx Electronics Air Conditioner 13ACX User Manual
LG Electronics Computer Monitor W2243S User Manual
LG Electronics Microwave Oven LMV2083SB User Manual
Linksys Network Card WPC54G User Manual
Marantz CD Player PMD325 User Manual
Metabo Cordless Sander RB 18 LTX 60 User Manual